Introduce:

The product are mainly from the oil tank ,high strength porcelain(or silicone rubber casing)base,corrugated expander,primary winding,secondary winding and other parts.

Mainfeatures:

  • Modern and compact design.
  • Small size,light weight,good insulation properties,high mechanical strength.
  • Uniform electric field distribution the dielectric loss factor .The partial discharge is low.
  • Inverted structure,the oil-paper insulation .Anti-current capability of dynamic thermal stability.Safe operation .Easy to maintain.
LVB-110W2
Rated voltage of system 110
Rated primary current 20*300-2*1500
Rated secondary current 5(1)
Class combination 5P/5P/5P/0.2S,5P/5P/5P/5P/0.5/0.2(0.2S)
Measure the level rated secondary load and instrument security factor 30-50VA FS<5 OR FS<10
Measure the level rated secondary load and the accuracy limit factor 30-60FVA 5P15-5P30
Short-time thermal current 50
Rated dynamic current 125
Creepage diatance >3150
Rated insulation level 126/200/480
Partial discharge level <5
Oil weight Total weight 60/340