HY-80 Low Voltage Current Transformer for Feeder Monitoring

The HY-80 low voltage current transformer features a 400/5A–2000/5A ratio range, Class 0.5/1.0 accuracy, 5–10VA burden, and 5A output. Ideal for AC current measurement, energy monitoring, and distribution panel metering.

The HY-80 low voltage current transformer provides a rated 5 A secondary output for feeder metering and load monitoring. Catalogue ratios range from 400/5 A to 2000/5 A, with Class 0.5 and Class 1.0 configurations. Three listed busbar sizes and a Ø60 mm circular opening support conductor matching.

Select the HY-80 by its current ratio, accuracy class, rated burden and conductor dimensions to match the measuring circuit and panel layout.

Key Features

  • Rated 5 A secondary output for instruments with a matching CT input.
  • Metering accuracy: Class 0.5 / Class 1.0 depending on ratio.
  • Rated burden: 5-10 VA according to the selected configuration.
  • Listed circular conductor opening: Ø60 mm.
  • Listed busbar dimensions: 80 × 10 / 60 × 30 / 50 × 50 mm.

Technical Specifications

Item Specification
Model HY-80
Product Type Closed-Core Low Voltage Current Transformer
Application AC Current Metering and Load Monitoring
Rated Secondary Current 5 A
Catalogued Ratio Range 400/5-2000/5 A
Accuracy Classes Class 0.5 / Class 1.0 depending on ratio
Rated Burden 5-10 VA according to ratio
Listed Busbar Dimensions 80 × 10 / 60 × 30 / 50 × 50 mm
Listed Circular Opening Ø60 mm

 

Dimensions and Conductor Fit

Refer to the HY-80 dimension drawing to check the opening profile, external dimensions and installation clearance. For cables, use the outside diameter including insulation. Allow space for the CT body and secondary wiring.

Current Ratio and Rated Burden

Current Ratio Class 0.5 Burden Class 1.0 Burden
400/5 A 5 VA 5 VA
500/5 A 5 VA 5 VA
600/5 A 5 VA 5 VA
750/5 A 10 VA 10 VA
800/5 A 10 VA 10 VA
1000/5 A 10 VA 10 VA
1200/5 A 10 VA 10 VA
1250/5 A 10 VA 10 VA
1500/5 A 10 VA 10 VA
1600/5 A 10 VA 10 VA
2000/5 A 10 VA 10 VA

 

Typical Applications

Distribution panel metering: Connect the HY-80 to a compatible ammeter or multifunction meter for feeder current measurement. Set the instrument to the selected CT ratio.

Energy monitoring: Supply current signals to compatible energy meters for individual feeders, production areas or building distribution circuits.

Motor feeder monitoring: Observe operating current and load changes through compatible measuring equipment.

Selection and Installation

Select ratio, accuracy class and burden together. Include the instrument burden and secondary cable losses when assessing the measuring circuit. Confirm conductor fit, 5 A input compatibility and polarity before connection.

Never leave the secondary circuit open while primary current is flowing. Use an appropriate shorting arrangement before disconnecting the instrument. Protection applications require separate technical assessment.

Ordering Information

Provide the HY-80 ratio, accuracy class, rated burden, conductor dimensions and order quantity. For selection assistance, include the meter specification and secondary cable length and cross-section.

Inquiry Now

    JOIN US

    Register as one of our members and provide you with the latest product and discount information.