Current transformer installation precautions
Things to note when installing current transformers in low-voltage distribution cabinets
1 When the current transformer is running, the secondary side is not allowed to be open.
2 The magnetic potential I1N1 of the current transformer’s primary measured current generates a magnetic flux Φ1 in the iron core;
3. The magnetic potential I2N2 of the current transformer’s secondary measuring instrument generates a magnetic flux Φ2 in the iron core;
4. The combined magnetic flux of the current transformer’s iron core: Φ=Φ1+Φ2;
5. Because Φ1 and Φ2 are in opposite directions and equal in magnitude, they cancel each other out, so Φ=0;
6. If the secondary is open, that is, I2=0, then: Φ=Φ1, the magnetic flux of the current transformer’s iron core is very strong, saturated, the iron core heats up, the insulation is burned out, and the Leakage;
7. If the secondary circuit is open, that is, I2=0, then: Φ=Φ1, Φ generates a very high induced potential e in the secondary coil N2 of the current transformer, forming a high voltage at both ends of the secondary coil of the current transformer, endangering the life safety of the operator;
8. One end of the secondary coil of the current transformer is grounded, which is a protective measure taken to prevent high voltage danger;
Therefore, fuses are not allowed to be connected in the secondary circuit of the current transformer, and it is not allowed to remove the ammeter, relay and other equipment without bypassing during operation.
Current transformer installation precautions

--- END ---
Dec 22, 2025
Cómo seleccionar correctamente transformadores de corriente para exteriores en Sudamérica: ejemplos de RECT y OCT de HEYI Electric En la construcción y operación de sistemas eléctricos en Sudamérica, la elección del transformador de corriente para exteriores es fundamental. Trabajo en un proyecto eléctrico. Busco un transformador de corriente que aumente la seguridad de los equipos.… Continue reading Cómo seleccionar transformadores de corriente para exteriores en
Dec 18, 2025
HEYI Electric: Providing complete solutions for power engineering projects in Malaysia, from current monitoring to status indication. The biggest challenge, for companies in Malaysias power sector is keeping the system reliable and making monitoring easy. HEYI Electric offers more, than measurement products. HEYI gives a set that includes precision current transformers, flexible current transmitters and… Continue reading Position indicator switch is used to create solutions for Malaysia.
Dec 11, 2025
In Egypt you must pick the CTs with care. The need is strongest, in Cairo, Alexandria and Suez because the electric grid often changes, gets hot and carries loads. When the CTs are not stable or not accurate the safety system can fail. I have seen that the switchgear, the fuse breakers and the CTs… Continue reading How to Choose the Right Current transformer in Egypt