Electromagnetic leakage protection characteristics robust design
Analysis of factors affecting the robustness of leakage protection characteristics
Influence of compensation capacitance dispersion on the robustness of protection characteristics
In order to analyze the influence of the dispersion of compensation capacitor C1 on the leakage action value, equation (2) can be obtained by transforming
(4)
Then the absolute sensitivity of C1 is
(5)
The relative sensitivity of C1 is
(6)
From equations (5) and (6), sensitivity curves with C1 under different inductance values can be obtained, as shown in Figure 12.
As can be seen from Figure 12, when the compensation capacitor is a resonant capacitor, the sensitivity is the lowest, that is, the action value is the most stable, but the action time is the longest. As can be seen from FIG. 12a, the absolute sensitivity is axisymmetrically C1=C0, and the change of excitation inductance L0 does not affect the change trend of absolute sensitivity. As can be seen from FIG. 12b, when C1 < C0, its relative sensitivity is generally smaller than when C1 > C0. The larger the excitation inductance, the smaller the relative sensitivity of C1. When L0≥250 H, the relative sensitivity S < 1.0 when C1 < C0, then the capacitance tolerance has little influence on the action value. Therefore, when the excitation induction is as large as possible and the compensation capacitor is smaller than the resonant capacitor, the relative sensitivity of the compensation capacitor can be reduced, that is, the influence of the dispersion of the compensation capacitor on the protection characteristics can be reduced.

Fig.12 Relationship between sensitivity and C1 under different L0
Since the action time changes in a ladder-like manner with the increase of compensation capacitance, the action time changes little on the same ladder. As can be seen from Figure 10, the influence of C1 tolerance on the action time can be reduced when C1 value is set in the middle of the ladder.
3.1.2 Influence of dispersion of magnetic parameters on robustness of protection characteristics
As can be seen from FIG. 11, when Br > 0.2T and Bs > 0.7T, the change curves of R1, C1 relationship and action time are relatively dense, and the action value and action time are less affected by the dispersion of Br. When Hc changes, the distance between R1 and C1 curves is large. Only when the value of compensating capacitor C1 is close to the value of resonant capacitor C0, the change of Hc has little effect on the action value. Under different magnetic parameters Br, Hc and Bs, the leakage action value and action time are simulated and calculated, and the results are shown in Figure 13.
The intersection points in FIG. 13a, 13c and 13e are the design points of protection characteristics under the parameters in Table 2. It can be seen that the change of Bs has the least impact on the action value and action time, while the change of Hc has the most impact. As can be seen from FIG. 13b, 13d and 13f, the change trend of action time is basically consistent with the action value, and the action time is relatively short when the capacitance is small. If the action value is close to IDn, the action time changes greatly, even exceeding the standard requirement of 300 ms. Therefore, in parameter design, it should be ensured that the action value is less affected by the dispersion of magnetic parameters, and there is a certain margin between the action value of rated residual current IDn.

Fig.13 Influence of magnetic parameters of residual current transformer on IDd and tC
In order to further clarify the influence of Bs on action value and action time, the changes of action value and action time with Br and Hc under different Bs were simulated and analyzed, as shown in FIG. 14.
It can be seen from FIG. 14 that under different Bs, the change curves of action value and action time with Br and Hc are very close, which proves that the change of Bs has the least influence on action value and action time. Therefore, in the design of magnetic properties parameters, Bs can be determined first, and then the influence of Br and Hc dispersion on the action value and action time can be analyzed. In this paper, Bs is determined to be 1.0T.
Compared with FIG. 13c and FIG. 14c, the influence of Hc change on action value and action time decreases after Br is increased. Under the conditions of Bs= 1.0T and Br= 0.2T, the R1 and C1 matching curves and action time curves of simulation analysis when Hc is 0.6, 0.7 and 0.8A /m, respectively, are shown in Figure 15. As can be seen from FIG. 15, the resonant capacitance values of the three groups are relatively close. When the compensation capacitor C1=18 nF, its values are close to the resonant capacitance values and are located in the gentle interval of the curve.

Figure 14 Influence of magnetic parameters on action value and action time under different Bs

Fig.15 Relationship curves of R1 and C1 and tC under different Hc
In summary, when the value of compensating capacitor C1 is determined, the design of Br and Hc makes the compensating capacitor C1 close to the resonant capacitor, which can reduce the influence of magnetic parameters on the action value and action time, and thus improve the robustness of leakage protection characteristics.
--- END ---
Feb 04, 2026
Why is single‑phase window type current transformer so popular in the South American electricity market? —Technical Analysis Based on the South American Power Bureau’s Bidding and Outdoor Environment In countries, like Brazil, Chile, Peru and Colombia the power infrastructure construction has kept growing in recent years. The distribution network upgrades, the energy grid integration and the… Continue reading Why single‑phase window type current transformer Dominate South America’s Power Grid
Feb 03, 2026
Why have single phase satuation current transformers (CTs) become an essential core component of switchgear in Southeast Asia? — Detailed technical analysis using the ICT series encapsulated transformer as an example. We examine the ICT series encapsulated transformer. In Asian countries such, as Malaysia, Indonesia, Thailand and Vietnam the low-voltage switchgear appears a lot in… Continue reading Why Single-Phase Saturation Isolation Current Transformers Are Essential in Switchgear
Jan 22, 2026
People use Current transmitter. Why do people use transmitters, in the chillers the air compressors, the generators and the IoT systems? In systems I see chillers, in commercial buildings air compressors in factories and generators, in data centers. The chillers, the air compressors and the generators all have one thing in common. In short devices… Continue reading Why Current Transmitter Matter in Chiller, Air Compressor, and Generator