How to Install a current transformer?
The secondary circuit conductors or cables should all be make of copper wires. The cross-section of the current transformer circuit conductor should not be less than 2.5mm2, and the cross-section of the voltage transformer circuit conductor should not be less than 1.5mm2.
The first terminal block at the current transformer outlet should use a dedicate current terminal, and the unused secondary winding of the current transformer should be short-circuit and ground at the terminal board.
There should be no joints in the secondary circuit wires in the panels and cabinets, and there should be no joints in the middle of the control cables or wires. If joints are necessary, a transition connection with a longer terminal box should be use.
The polarity of the current transformer cannot be reverse, and the phase sequence and phase difference should comply with the design and regulations. For the transformer wiring for differential protection, the current phasor diagram of both arms must be measured before it is put into operation to verify the correctness of the wiring.
The secondary circuit wires should be arrange neatly and aesthetically. Additionally, the connecting screws between the wires and electrical components, as well as terminal blocks, must not be loose. Moreover, the distance between the wire binding points should comply with the requirements specified in the regulations.
The insulation of the secondary circuit to the ground should be good, and there should be no mixing of wires between the voltage circuit and the current circuit.
Both the current and voltage circuits should ground at one point at the secondary side outlet of the transformer.
--- END ---
Oct 21, 2025
An important component of data center power monitoring : HEYI Electric HYB-A1 4-20mA current transmitter Why data centers cannot do without current transmitters In the digital information age , data centers are the core of the Internet . We not only need excellent server performance, low network latency , and huge storage capacity, but we… Continue reading Why is 4-20mA current transmitter suitable for data centers
Oct 18, 2025
Battery current sensor from HEYI Electric – Providing Safer Protection for Clean Energy Why clean energy systems cannot do without leakage detection Carbon neutrality is the common goal of the earth. In an era when clean energy is becoming increasingly popular – from electric vehicle charging stations to photovoltaic power generation systems and energy storage… Continue reading How battery current sensor serve clean energy
Oct 09, 2025
HEYI Electric’s SDH Window-type CT : a universal player for European and American projects Two frequency options : 50Hz /60Hz for Europe and 60Hz for North America. One set of assembly design is universally applicable worldwide , so there is no need to distinguish two sets of product numbers for cross-border and cross- regional projects… Continue reading Window-type CT suitable for EURO and US projects