CTK Type Zero-sequence Current Transformer

Introduce:

CTK Series zero-sequence current transformers are used inconjunction with relay protection devices or signals when thepower system generates zero-sequence grounding current, sothat the device components can operate to achieve protectionor monitoring.

When an electric shock or leakage fault occurs in the circuit.the secondary side of the transformer outputs a zero-sequencecurrent, so that the equipment on the connected secondarv linewill be protected (cut off the power supply, alarm, etc.)

Mainfeatures:

  • Detection of unbalanced current: ZCT is designed to measure the unbalanced current in a three-phase electrical system, which is the sum of the three phase currents. This allows them to detect ground faults, which can occur when a fault current flows from one or more of the phase conductors to ground.
  • High sensitivity: ZCT is highly sensitive and can detect even small amounts of ground fault current. This helps to prevent damage to equipment and reduce the risk of electric shock to personnel.
  • Accuracy: ZCT is designed to provide accurate measurements of the zero-sequence component of the current, even in the presence of high levels of noise or interference.
  • Non-intrusive installation: ZCT is typically installed around the neutral conductor of a three-phase system, which means that they can be installed without the need to break the circuit or interrupt power to the load.
  • Frequency response: ZCT is designed to operate over a wide range of frequencies, typically from 50Hz to 400Hz, which makes them suitable for use in a variety of applications.
  • Low burden: ZCT is designed to have a low burden, which means that they do not significantly affect the operation of the circuit or the accuracy of other measurement devices in the system.

Application:

  • Electric fire monitorin
  • Fire prevention and leakage protection system
  • Electromagnetic relaying protection
  • Microcomputer protection, etc.
Electrical parameters Mechanical parameters
Frequency 50~400Hz Shell ABS(flame retardant grade 94-V0)
Rated input 10mA~5A Bobbin PBT
Measuring range 10%In~130%In iron core Ni steel/nanocrystalline
Rated output 0~1v (A or) 0~0.25mA Internal structure Environmentally friendly epoxy resin casting
Ratio difference ≤±0.1% Construction plan Screw fixing
Phase difference ≤±10 Working temperature -25℃~ +75℃
Dielectric Strength 2.5KV/1mA/1min Ambient Humidity ≤85%
Insulation resistance DC500V/1000MΩ/min Wiring method Terminal type/shielded twisted wire 1.5m
Model Specifications Dimensions
Reference current ø A B C D E
CTK-45 ≤100A 45 104 81 95 5 28
CTK-65 ≤225A 65 124 101 115 5 28
CTK-80 ≤400A 80 138 116 130 5 28
CTK-100 ≤630A 100 158 136 150 5 28
Electrical parameters Mechanical parameters
Frequency 50~400Hz Shell ABS(flame retardant grade 94-V0)
Rated input 10mA~5A Bobbin PBT
Measuring range 10%In~130%In iron core Ni steel/nanocrystalline
Rated output 0~1v (A or) 0~0.25mA Internal structure Environmentally friendly epoxy resin casting
Ratio difference ≤±0.1% Construction plan Screw fixing
Phase difference ≤±10 Working temperature -25℃~ +75℃
Dielectric Strength 2.5KV/1mA/1min Ambient Humidity ≤85%
Insulation resistance DC500V/1000MΩ/min Wiring method Terminal type/shielded twisted wire 1.5m
Model Specifications Dimensions
Reference current ø A B C D E
CTK-45 ≤100A 45 104 81 95 5 28
CTK-65 ≤225A 65 124 101 115 5 28
CTK-80 ≤400A 80 138 116 130 5 28
CTK-100 ≤630A 100 158 136 150 5 28

Dimensions

CTK Type Zero-sequence Current Transformer-heyi

    Inquiry Now