Products Type
Contact Us

HEYI Electrical CO.,LTD

Contact person: Bethy

Position: Sales Manager

Tel: 86-577-62659558

Fax: 86-577-61712987

Mobile: 86-13968747975

E-mail: heyi@heyiele.com

bethy@heyiele.com

Skype: bethycai

ADD: #21 ShangYou North 

Road, HuangHua LiuShi YueQing,

Zhe Jiang, CHINA

http://www.heyiele.com

Product

Home » Product
 D1

 

D1 series current sensor is a closed loop device based on the principle of the hall effect, with a galvanic isolation between primary and secondary circuit. It provides accurate electronic measurement of DC, AC or pulsed  currents.

Electrical data (Ta=25℃±5)

Type

D1-50A

D1-100A

D1-200A

D1-300A

Unit

Rated current(Ipn)

±50

±100

±200

±300

A

Measure range(Ip)

0—±75

0—±150

0—±300

0—±350

A

Turns ratio(Np/Ns)

1:1000

1:1000

1:2000

1:2000

T

Measure resister

0~200

0~200

0~80

0~50

Ω

Coil resister

12.5

12.5

27.5

27.5

Ω

Rated output

50

100

100

150

mA

Supply voltage

±12,±15

V

Power Consumption

≤20+IpX(Np/Ns)

mA

Offset current

@Ip=0                        ±0.15

mA

Offset drift

@ -40~+85℃                 ≤±0.4

mA

Linearity

@Ip=0-±Ipn                   ≤0.1

%FS

Response time

@50A/μS, 10%-90%            ≤1

μS

Galvanic isolation

@ 50HZ,AC,1min                3

KV

di/dt

>100

A/us

Bandwidth

@ -3dB                       0~100

KHZ

Applications

 ·Variable speed drives

·Welding machine

·Battery supplied applications

·Uninterruptible Power Supplies (UPS)

·Electrochemical

Mechanical dimension(for reference only)

 

Remarks

1. All dimensions are in mm.

2. General tolerance ±1mm.

3. Elucidation:  1:+15V  2:–15V  3:I0UT  4:NC
Directions for use 

1. When the current will be measured goes through a sensor, the current will be measured at the output end.(Note: The false wiring may result in the damage of the sensor)

2. Custom design in the different rated input current and the output current are available.

Standards 

·UL94-V0.

·EN60947-1:2004

·IEC60950-1:2001

·EN50178:1998

·SJ 20790-2000
General date

 

Value

Unit

Operating temperature(TA)

-40 to +85

Storage temperature(TS)

-40 to +125

Mass(approx) (M)

43

g

Characteristics chart

 

Inquiry Form
Products Images:
Produt: D1
Full Name: *
Address:
Phone:
Email Address: *
Message: *
Upload Photos:
Contact Online bethycai 285611779 86-13968747975 bethy@heyiele.com